Provides five digital Inputs using a specific resistor-to-resistor network connected to universal Input. Allows a single universal input (with capability to measure resistance between 700 Ohm to 1600 Ohm) to monitor the status of up to five dry contacts.
Convert 1 UI to 5 DI, only for 30P, cannot be used with FG, FW or FC series
Features:
24VAC or 24DC power supply input.
Status Indicator: Built-in power and input LEDs indication and diagnostic purpose.
Jumper: Built-in internal jumpers for easy diagnostic.
Relay Drive: External dry contact is driven by relay supports higher impendence load.
Ease of Installation: All I/Os are connected via field removable terminal block connectors for easy maintenance. The controller casing fits standard DIN rail mounting.